4.6
Calibration Group
Calibration Data
Refer to Section 5 Calibration for complete calibration information and instructions.
4.7
Status Group
Status Test Data
Table 4-6 lists all the function prompts in the Status group. All prompts are read-only and provide the
status of the background diagnostic tests.
Function Prompt
(Lower Display)
Software Version
VERSION
RAM TEST
Status of RAM test performed in
background
Status of Configuration
CONFTEST
Checksum test performed in
background
Status of Working Calibration
CAL TEST
test performed in background
4.8
P.I.E. Tool Ethernet and Email Configuration Screens
Introduction
These screens only appear in instruments that have Ethernet Communications. Ethernet and Email
parameters can only be configured via the Process Instrument Explorer (P.I.E. Tool
section show screen-shots of the Configuration Screens from the PC version of the P.I.E. Tool
Configuration Screens are generally similar in format but smaller.
Ethernet Configuration Screen
This controller is shipped from the factory with the IP Address set to 10.0.0.2, the Subnet Mask set to
255.255.255.0 and the Default Gateway set to 0.0.0.0. Consult your Information Technologies (IT)
9/06
7866 Triple Range Digital H
Table 4-6 Status Group Function Prompts
Function Name
and CO
Analyzer/Indicator - Operation and Maintenance
2
2
Read Only Displays
(Upper Display)
7866_n
The first number set (7866) details the unit class as the
7866 product and the next number set gives the software
version.
PASS or FAIL
If status was FAIL, cycle power to see if error clears. If
problem persists, the unit is bad and should be replaced.
PASS or FAIL
If status was FAIL, completion of test results in
re-computation of checksum and a new status of PASS. All
configuration parameters should be rechecked for
accuracy.
PASS or FAIL
If status was FAIL, completion of test results in
re-computation of CRC value. All calibration of inputs and
outputs should be verified for accuracy.
Set Up Mode
®
). The figures in this
®
. Pocket PC
39