Static Parameters Of The 2 Ai I Electronic Module - Siemens Metro 21 M216KA Operator's Manual

Distributed i/o device
Table of Contents

Advertisement

SC Analog Electronic Modules – T echnical Data
Parameters
Table 12-3

Static Parameters of the 2 AI I Electronic Module

Parameter
Measurement type
Measurement range (4-wire
measuring transducer)
Interference frequency sup-
pression
Smoothing
Format
Default Parameters
12-16
The 2 AI I electronic module uses the following parameters:
Value Range
Deactivated
Current (4-wire measuring
transducer)
4...20 mA
20 mA
50 Hz (integration time 60
ms)
60 Hz (integration time 50
ms)
None
Weak
Medium
Strong
SIMATIC S7
SIMATIC S5
If you have not set the parameters of the 2 AI I electronic module using the
specified software (see Chapter 4), the default settings apply to both input
channels after a restart (see Table 12-3).
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Default Parameters
Current (4-wire measuring
transducer)
4...20 mA
50 Hz
None
SIMATIC S7
Scope
Channel
Channel
Module
Channel
Channel
EWA 4NEB 780 6009-02c