Disconnector And Three-Position Disconnector - Siemens 8DB10 Installation And Operating Instructions Manual

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

Description
Function of three-position
disconnector
Function of disconnector
24/214
10

Disconnector and three-position disconnector

Busbar system 1 is equipped with a the three-position disconnector which combines the
functions of a disconnector and an earthing switch. It is designed for no-load operation only.
A disconnector is installed in busbar system 2. It is designed for no-load operation only.
The disconnector has a work-in-progress earthing contact for maintenance work,
which cannot be operated during normal operation.
ATTENTION
The work-in-progress earthing contact of the disconnector in busbar system 2 is designed for
maintenance work at the three-position disconnector in busbar system 1 in de-energized
condition only.
➭ Before switching to the work-in-progress earthing contact, always contact your regional
Siemens representative.
Fig. 7:
8DB three-position disconnector for busbar
system 1 and three-position disconnector
for busbar system 2
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
Fixed contact of busbar,
busbar system 1
Fixed contact of busbar,
busbar system 2
Work-in-progress earthing contact
for system 2
Moving contact for
system 2 in OPEN position
Bushing
Fixed contact for
READY-TO-EARTH, system 1
Moving contact for
system 1 in OPEN position