8.3.2
Bus connector
Wiring
Only with 6ES7467-5GJ02-0AB0.
The bus cable is connected to the IM 467 by means of this connector. (See the detailed
description in the section on networking in the
3
Figure 8-3
(1)
(2)
(3)
Maximum cable lengths for PROFIBUS DP
Transmission speed
Max. length of a bus
Max. number of bus
Max. length in m
Bus segments are interconnected with RS 485 repeaters
1
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
2
Connecting the bus connector to the IM 467
Switch for bus terminator resistor
PROFIBUS_DP bus line
Bus connector
9,6
in Kbps
1.000
segment in m
10
segments 1
10.000 10.000 10.000 10.000 4.000
PROFIBUS DP master interface IM 467/IM 467 FO
S7-400, Hardware and Installation manual .)
1
19,2
93,75
187,5
1.000
1.000
1.000
10
10
10
8.3 Connection to PROFIBUS DP
500
1500
3000
400
200
100
10
10
10
2.000
1.000
6000
12000
100
100
10
10
1.000
1.000
369