S5 interface IM 463-2

7.1

Using SIMATIC S5 expansion units in an S7-400

Order number
6ES7463-2AA00-0AA0
Area of application
The IM 463-2 interface module is used for distributed connection of S5 expansion units to an
S7-400. You can use the IM 463-2 in the CR of the S7-400. You can use an IM 314 in the S5
expansion unit.
This allows you to connect the following S5 expansion units to an S7-400:
● EG 183U with IM 314 in slot 3
● EG 185U with IM 314 in slot 3
● EG 186U with IM 314 in slot 3
● ER 701-2 with IM 314 in slot 7
● ER 701-3 with IM 314 in slot 7
Accordingly, you can use all digital and analog I/O modules suitable for these EUs or ERs.
Basic requirement
If you connect an S5 expansion unit to a CR of the S7-400 via an IM 463-2, the SIMATIC S5
basic requirements concerning EMC, ambient conditions, etc., apply for the overall system.
Note
In environments contaminated by radiated noise, you must apply the type 721 cable shield
(see
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Installation manual ).