hit counter script

Siemens SIMATIC S7-400 Reference Manual page 117

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Setting the input delay for channel groups
You can only set the input delay for each group of channels. In other words, the setting for
channel 0 applies to inputs 0 to 7 and the setting for channel 8 applies to inputs 8 to 15.
Note
The parameters that are entered for the remaining channels (1 to 7 and 9 to 15) must be equal
to the value 0 or 8, otherwise those channels will be reported as being incorrectly configured.
Any hardware interrupts that have occurred in the meantime will be reported after
acknowledgement.
Optimum signal propagation delays
You can achieve the fastest signal propagation delay with the following settings:
● Both channel groups are configured with an input delay of 0.5 ms
● The diagnostics parameter is disabled
● The diagnostic interrupt parameter is disabled
Circuit as for active high or active low input
L+
U_s
0V
U_s
- L+
Figure 4-7
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
4.10 Digital input module SM 421; DI 16 x UC 24/60 V (6ES7421-7DH00-0AB0)
Active high
Source input
L+
"1"
U_s
"0"
0V
"1"
- L+
Input threshold
Circuit as for active high or active low input
DI_x
DI_xN
U_s
"0"
"1"
Digital modules
Channel x of the
SM 421 DI 16xUC 24/60 V
117