Siemens SIMATIC S7-400 Reference Manual page 297

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Crosstalk between the inputs
Operational limit (throughout temperature range, relative to input range)
● RTD input
Basic error limit (operational limit at 25°C, relative to input range)
● RTD input
Linearity error (relative to input range)
● RTD input
Repeat accuracy (in settled state at 25°C, relative to
input range)
● RTD input
Interrupts
● Hardware interrupt
● Hardware interrupt when limit value exceeded
● Diagnostic interrupt
Diagnostic functions
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
5.24 Analog input module SM 431; AI 8 x RTD x 16 Bit (6ES7431-7KF10-0AB0)
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
> 70 dB
RTD-4L RTD-3L
±1.8 °C ± 3.4 °C
± 0.8 °C ± 1.7 °C
± 0.4 °C ± 0.7 °C
± 0.3 °C ± 0.4 °C
± 1.5 °C ± 2.1 °C
± 0.2 °C ± 0.3 °C
RTD-4L RTD-3L
± 0.5 °C ± 1.0 °C
± 0.3 °C ± 0.5 °C
± 0.3 °C ± 0.4 °C
± 0.2 °C ± 0.2 °C
± 0.3 °C ± 0.6 °C
± 0.2 °C ± 0.2 °C
Additional fault
RTD-4L RTD-3L
± 0.2 °C ± 0.3 °C
± 0.2 °C ± 0.2 °C
± 0.1 °C ± 0.1 °C
± 0.1 °C ± 0.1 °C
± 0.1 °C ± 0.2 °C
± 0.1 °C ± 0.1 °C
Additional fault
RTD-4L RTD-3L
± 0.2 °C ± 0.3 °C
± 0.2 °C ± 0.2 °C
± 0.1 °C ± 0.1 °C
± 0.1 °C ± 0.1 °C
± 0.1 °C ± 0.2 °C
± 0.1 °C ± 0.1 °C
Status, interrupts, diagnostics
Configurable
Configurable
Configurable
Configurable
Analog modules
297