Table 5-11
Representation of analog values in the voltage measuring ranges 1 to 5 V and 0 to 10 V
System
Dec.
118,515 % 32767
117,593 % 32512
117,589 % 32511
27649
100,000 % 27648
75 % 20736
0,003617 % 1
0 % 0
- 1
- 17,593 % - 4864
≤-17,596 %
32767
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Hex.
1 to 5 V
7FFF
5.741 V
7F00
7EFF
5.704 V
6C01
6C00
5 V
5100
3.75 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
7FFF
5.4 Representation of analog values
Voltage measuring range
0 to 10 V
11.852 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
Negative values are not
supported
Analog modules
Overflow
Overshoot range
Nominal range
Undershoot range
Wire break
173