PROFINET standard
The S7-1500 automation system/ET 200MP distributed I/O system is based on standard
IEC 61158 Type 10.
PROFIBUS standard
The S7-1500 automation system/ET 200MP distributed I/O system is based on standard
IEC 61158 Type 3.
Marine approval
Classification societies:
● ABS (American Bureau of Shipping)
● BV (Bureau Veritas)
● DNV-GL (Det Norske Veritas - Germanischer Lloyd)
● LRS (Lloyds Register of Shipping)
● Class NK (Nippon Kaiji Kyokai)
● KR (Korean Register of Shipping)
● CCS (China Classification Society)
Industrial use
The S7-1500 automation system ET 200MP / distributed I/O system is designed for the
industrial field. It meets the following standards for this type of use:
● Requirements on interference emission EN 61000-6-4: 2011
● Requirements on immunity EN 61000-6-2: 2005
Use in mixed areas
Under certain conditions you can use the S7-1500 automation system ET 200MP /
distributed I/O system in a mixed area. A mixed area is used for residential purposes and for
commercial operations that do not significantly impact the residential purpose.
If you use the S7-1500 automation system / ET 200MP distributed I/O system in a mixed
area, you must comply with the radio frequency interference limits of the generic standard
EN 61000-6-3. Suitable measures for observing these limits for use in a mixed area are, for
example:
● Installation of the S7-1500 automation system / ET 200MP I/O system in grounded
control cabinets
● Use of noise filters in the supply lines
An additional individual acceptance test is also required.
Automation system
System Manual, 12/2017, A5E03461182-AE
Technical specifications
16.1 Standards and Approvals
317