hit counter script

11.7 Backing Up And Restoring The Cpu Configuration - Siemens Simatic S7-1500/ET 200MP System Manual

Automation system
Hide thumbs Also See for Simatic S7-1500/ET 200MP:
Table of Contents

Advertisement

Commissioning

11.7 Backing up and restoring the CPU configuration

11.7
Backing up and restoring the CPU configuration
Backup from online device
You will make a number of changes to your plant over time, for example, add new devices,
replace existing devices or adapt the user program. If these changes result in undesirable
behavior, you can restore the plant to an earlier state. Before you load a changed
configuration to the CPU, first use the option "Backup from online device" to create a
complete backup of the current device status.
Upload from device (software)
With the option "Upload from device (software)", you load the software project data from the
CPU to an existing CPU in the project.
Upload device as new station
If you are operating a new programming device/PC in the plant, the STEP 7 project that was
used to create the plant configuration might not be available. In this case you can use the
option "Upload device as new station" to load the device's data into a project in your PG/PC.
Snapshot of the monitor values
You can use the option "Snapshot of the monitor values" to backup the current values of the
data block, in order to be able to restore the current values if necessary at a later date.
Overview of backup types
The table below shows the backup of CPU data depending on the selected type of backup
and its specific characteristics:
Actual values of all DBs
(global and instance data blocks)*
Blocks of the type OB, FC, FB and
DB
PLC tags
(tag names and constant names)
Technology objects
Hardware configuration
Actual values (bit memories, tim-
ers, counters)*
Contents of the SIMATIC memory
card
Archives, recipes
Entries in the diagnostics buffer
Current time
Backup possible for fail-safe CPUs
Backup can be edited
Backup possible in operating mode
* Only the values of the tags that are set as retentive are backed up
244
Backup from online
Upload from device
device
--
--
Properties of the type of backup
--
STOP
RUN, STOP
Upload device as
(software)
new station
--
--
--
--
--
--
--
RUN, STOP
System Manual, 12/2017, A5E03461182-AE
Snapshot of the
monitor values
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
RUN, STOP
Automation system