2.2.7.36 Registers 5201 to 5299: Latest 10 Swells (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value + Date/time
The following table shows the information for the latest swell (5201 to 5209). The information of the other 9
swells (5211 to 5299) are in the same structure.
Table 2-45
Register
5201
5202
5203
5204
5205 to 5206
5207 to 5208
5209
2.2.7.37 Registers 5401 to 5499: Latest 10 Voltage Interrupts (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value + Date/time
The following table shows the information for the latest voltage interrupt (5401 to 5409). The information of the
other 9 voltage interrupts (5411 to 5499) are in the same structure.
Table 2-46
Register
5401
5402
5403
5404
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
Registers 5201 to 5209: The Latest Swell
Type of Information
Milliseconds
Hours/minutes
Month/day
Time status/year
Voltage swell 1
Voltage swell 1 time duration
Influenced phase
Registers 5401 to 5409: The Latest Voltage Interrupt
Type of Information
Milliseconds
Hours/minutes
Month/day
Time status/year
Unit
Start time of swell
Data format see chapter 2.2.6.2
V
Maximum voltage value during swell 1
s
Swell 1 time duration
-
Related phases
bit 0: Va, bit 1: Vb, bit 2: Vc,
bit 3: Vab, bit 4: Vbc, bit 5: Vca
if any bit =1 means corresponding phase
is influenced
Unit
Start time of interrupt
Data format see chapter 2.2.6.2
Communication
2.2 Modbus
Remark
Remark
67