Communication
2.2 Modbus
The following table shows the BI status of the SICAM IO subdevice 1 (0135). The BI status of the SICAM IO
subdevice 2 (0137) are in the same structure.
Table 2-14
Register
0
0135/2
2
0135/2
4
0135/2
6
0135/2
8
0135/2
10
0135/2
12
0135/2
14
0135/2
36
Register 0135: Status of Binary Inputs of SICAM IO Subdevice 1
Type of Information
Binary input 1-N SICAM IO 1,
terminals N8/9
Binary input 2-N SICAM IO 1,
terminals N9/10
Binary input 3-N SICAM IO 1,
terminals N11/12
Binary input 1-P SICAM IO 1,
terminals P8/9
Binary input 2-P SICAM IO 1,
terminals P9/10
Binary input 3-P SICAM IO 1,
terminals P11/12
Reserved
SICAM Subdevice 1 OK
Remark
The statuses of the binary inputs are read from the
SICAM IO 7XV5673 connected as subdevice 1.
Value = 0 and status = invalid are transmitted when the
indication Subdevice 1 OK = 0.
The communication to SICAM IO 7XV5673 is inter-
rupted.
= 0
Communication with the SICAM IO 7XV5673 is:
0 = interrupted
1 = established
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020