Type designation key
The type designation contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (eg, ACS880-07-240A-5). The
optional selections are given thereafter, separated by plus signs, eg, +E202. The main
selections are described below. Not all selections are available for all types. For more
information, refer to ACS880-X7 single drives ordering information (3AXD10000052815,
available on request).
Basic codes
■
Code
Description
ACS880
Product series
07
When no options are selected: cabinet-installed drive, IP22 (UL Type 1), main switch-disconnector
(switch fuse with aR fuses), ACS-AP-W assistant control panel with Bluetooth interface, no EMC
filter, built-in input DC choke (frames R6 to R9), built-in input AC choke (frames R10 and R11),
coated boards, ACS880 primary control program, Safe torque off function, bottom entry and exit of
cables, multilingual device label sticker, USB memory containing circuit diagrams and all manuals.
Size
xxxx
See
Ratings (page
Voltage range
3
380...415 V. This is indicated in the type designation label as typical input voltage level 3 ~ 400 V AC.
5
380...500 V. This is indicated in the type designation label as typical input voltage levels 3 ~
400/480/500 V AC.
7
525...690 V. This is indicated in the type designation label as typical input voltage levels 3 ~
525/600/690 V AC.
Option codes
■
Code
Description
B054
IP42 (UL Type 1 Filtered)
B055
IP54 (UL Type 12)
C121
Marine construction. See section
Air inlet through bottom of cabinet. See section
C128
+C128) (page
UL Listed (evaluated to both U.S. and Canadian safety requirements). See section
C129
+C129) (page
C130
Channeled air outlet. See section
Marine type approval. Refer to ACS880 +C132 marine type-approved cabinet-built drives supplement
C132
(3AXD50000039629 [English]).
C134
CSA approved. See section
C164
Plinth height 100 mm. See section
C179
Plinth height 200 mm. See section
C180
Seismic design. See section
Empty 400 mm wide cubicle on right. See section
C196
+C196...C198) (page
Empty 600 mm wide cubicle on right. See section
C197
+C196...C198) (page
197).
Marine construction (option +C121) (page
82).
50).
Channeled air outlet (option +C130) (page
CSA Approved (option +C134) (page
Plinth height (options +C164 and +C179) (page
Plinth height (options +C164 and +C179) (page
Seismic design (option +C180) (page
51).
51).
Operation principle and hardware description 59
Air inlet through the bottom of cabinet (option
51).
51).
Empty cubicles on right (options
Empty cubicles on right (options
50).
UL Listed (option
50).
51).
51).