ABB ACS880 User Manual

ABB ACS880 User Manual

Industrial drives, atex-certified motor thermal protection functions for cabinet-built acs880 drives (options +l513+q971 and +l514+q971)
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

ABB INDUSTRIAL DRIVES
User's manual
ATEX-certified motor thermal protection
functions for cabinet-built ACS880 drives
(options +L513+Q971 and +L514+Q971)

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS880

  • Page 1 — ABB INDUSTRIAL DRIVES User’s manual ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives (options +L513+Q971 and +L514+Q971)
  • Page 2 3AUA0000101764 cabinets Electrical planning instructions for ACS880 multidrive cabinets 3AUA0000102324 and modules Drive hardware manuals ACS880-07 (45 to 630 kW, 50 to 700 hp) hardware manual 3AUA0000105718 ACS880-07 (560 to 2800 kW) hardware manual 3AUA0000143261 ACS880-17 drives hardware manual 3AXD50000020436...
  • Page 3 User’s manual ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives (options +L513+Q971 and +L514+Q971) Table of contents  2019 ABB Oy. All Rights Reserved. 3AXD50000014979 Rev C EFFECTIVE: 2019-05-22...
  • Page 5: Table Of Contents

    PTC thermistor relays ........... 20 ABB CM-MSS.41 thermistor motor protection relay ......21 Layout .
  • Page 6 ABB CM-MSS.41 ........
  • Page 7 Control circuit S1-T2 ..........56 Indication of operating states .
  • Page 8 Providing feedback on ABB Drives manuals ....... . . 79...
  • Page 9: Introduction To The Manual

    This chapter contains information on the manual, gives safety instructions and other general information for the reader. Applicability The manual applies to cabinet-built ACS880 single drives and multidrives with the options: • +L513+Q971 and +2L513+Q971 (+3L513+Q971 available as an application-engineered option) •...
  • Page 10: Example Circuit Diagrams Of This Manual

    The function described in this manual activates the Safe torque off (STO) function of the drive/inverter unit. The STO function of the ACS880 drives is certified (SIL 3 according to EN/IEC 61800-5-2 and IEC 61508). For a detailed description of the STO function, see the hardware manual of your drive/inverter unit.
  • Page 11: Commissioning The Drive For A Motor In A Hazardous Area

    ATEX/Ex regulations. Contents This manual contains information on implementing the ATEX-certified motor thermal protection functions in the ACS880 cabinet-built drives, as well as the ATEX certification documents. This manual consists of the following chapters: •...
  • Page 12: Terms And Abbreviations

    With the ACS880-07 (smaller), the frame size marking of the drive indicates the physical size of the drive, eg, R6. With the ACS880-07 (larger), the frame size marking of the...
  • Page 13: Exclusion Of Liability

    Exclusion of liability ABB is not responsible for the implementation, verification and validation of the overall safety system. It is the responsibility of the end user (or other party) who is responsible for the overall system, system safety and compliance with ATEX/Ex regulations.
  • Page 14 14 Introduction to the manual...
  • Page 15: Atex-Certified Motor Thermal Protection Function With Ptc Thermistor Relays

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 15 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) Contents of this chapter This chapter describes the ATEX-certified motor thermal protection function (option +L513+Q971) and gives instructions on how to wire, install and start up the function.
  • Page 16: Description

    ACS880-07 drives, frames nxDXT + nxR8i with a main contactor/breaker (option +F250/ +F255) and ACS880-17/37 drives, frames nxR8i + nxR8i: When the STO function is activated in the inverter unit, the main contactor/breaker is opened after user-defined delay (defined with parameter 94.11, the default value is 600 s). See hardware and firmware manuals for more information.
  • Page 17: Operation Principle

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 17 Operation principle  Without an FSO module 1. When the motor temperature rises to the thermistor wake-up level, the resistance of the thermistor increases sharply. 2. The PTC thermistor relay detects the change and indicates motor overtemperature through its output contacts.
  • Page 18: With An Fso Module

    18 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) With an FSO module 1. When the motor temperature rises to the thermistor wake-up level, the resistance of the thermistor increases sharply. 2. The PTC thermistor relay detects the change and indicates motor overtemperature through its output contacts.
  • Page 19: Resetting The Atex-Certified Motor Thermal Protection Function

    FSO module by connecting a reset circuit to the FSO module (see page 46). ACS880-07/17/37 drives with the option +Q978 or +Q979 (Emergency stop): In these safety functions, a reset circuit is connected to the FSO module and the user must reset the safety function with the emergency stop reset button.
  • Page 20: Ptc Thermistor Relays

    PTC thermistor relays The ATEX-certified motor thermal protection function contains one (+L513) or two (+2L513) ABB CM-MSS.41 thermistor relays by default. Three ABB CM-MSS.41 thermistor relays (+3L513) are available as an application-engineered option. DOLD MK 9163N.12/110-ATEX thermistor relay(s) are available by request.
  • Page 21: Abb Cm-Mss.41 Thermistor Motor Protection Relay

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 21 ABB CM-MSS.41 thermistor motor protection relay  Layout A1-A2 Power supply T1-T2 Measuring circuit with 1…3 sensors. S1-T2 Remote reset push button switch WARNING! Even though autoreset of the relay can be...
  • Page 22: Dold Mk 9163N.12/110-Atex Thermistor Relay

    22 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) DOLD MK 9163N.12/110-ATEX thermistor relay  Layout A1(+) A1-A2 Power supply P1-P2 Measuring circuit with 1…6 sensors X1-X2 Remote reset push button switch 11-12/14 Output contacts (1) • 11: Common •...
  • Page 23: Wiring

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 23 Wiring General wiring instructions  1. Wire only the PTC sensor circuit into the potentially explosive atmosphere. 2. The installation of the PTC sensor circuit in the Ex Zone must comply with the requirements for the applicable type of protection, such as: •...
  • Page 24: Wiring Example

    24 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) Wiring example  In this example, contacts of the PTC thermistor relay(s) are wired to digital input DI6 of the drive control unit for indication purposes. 1. Connect the PTC sensor(s) of the motor to the PTC thermistor relay(s) [K74] (and [K75] and [K76] if present) through terminal block [X506].
  • Page 25: Start-Up And Acceptance Test

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 25 Start-up and acceptance test You need the Drive composer PC tool or a control panel to perform the start-up and acceptance test. If you have to set FSO module parameters, you need the Drive composer pro PC tool. Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
  • Page 26: Maintenance

    26 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) Maintenance After the operation of the safety circuit has been verified at start-up, the circuit requires a periodic proof test at least every two years. If you change any wirings or components related to the motor thermal protection function after the start-up, repeat the procedure given in section Start-up and acceptance test above.
  • Page 27: Safety Data And Block Diagrams

    ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 27 Safety data and block diagrams The safety block diagrams show the components that are included in the safety data calculations. Without an FSO module  Thermistor Drive STO Customer relay(s) motor PTC sensor(s)
  • Page 28 28 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
  • Page 29: Contents Of This Chapter

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 29 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) Contents of this chapter This chapter describes the ATEX-certified motor thermal protection function (option +L514+Q971) and gives instructions on how to wire, install and start up the function.
  • Page 30: Description

    ACS880-07 drives, frames nxDXT + nxR8i with a main contactor/breaker (option +F250/ +F255) and ACS880-17/37 drives, frames nxR8i + nxR8i: When the STO function is activated in the inverter unit, the main contactor/breaker is opened after user-defined delay (defined with parameter 94.11, the default value is 600 s). See hardware and firmware manuals for more information.
  • Page 31: Pt100 Relays

    The used Pt100 relays are [Ex i] (intrinsically safe) approved associated apparatus (Ex i barrier). The installation and cabling of the protection circuit in the ACS880 cabinet is done as intrinsically safe according to EN/IEC 60079-14 ed. 5 clause 16.
  • Page 32: Operation Principle

    32 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) Operation principle Without an FSO module  1. When the motor temperature rises, the sensor resistance increases linearly. 2. When the motor temperature exceeds the set operating temperature limit of the Pt100 relay, the relay indicates motor overtemperature through its output contacts.
  • Page 33: With An Fso Module

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 33 With an FSO module  1. When the motor temperature rises, the sensor resistance increases linearly. 2. When the motor temperature exceeds the set operating temperature limit of the Pt100 relay(s), the relay indicates motor overtemperature through its output contacts.
  • Page 34: Resetting The Atex-Certified Motor Thermal Protection Function

    FSO module by connecting a reset circuit to the FSO module (see page 46). ACS880-07/17/37 drives with the option +Q978 or +Q979 (Emergency stop): In these safety functions, a reset circuit is connected to the FSO module and the user must reset the safety function with the emergency stop reset button.
  • Page 35: Pt100 Relays

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 35 Pt100 relays The option contains three (+3L514), five (+5L514) or eight (+8L514) GM International D1073S relays by default. PRelectronics 9116B1 relays are available as application engineered. The option also contains one, two or three DOLD LG5925.48 extension relays in the Safe torque off and diagnostic circuits.
  • Page 36: Prelectronics 9116B1 Universal Converter Relay (Programmable)

    36 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) PRelectronics 9116B1 universal converter relay (programmable)  Layout 32-31 Power supply • 32: +24 V DC • 31: 0 V DC 33-34 Status relay in safe area (Not used in the particular application described by this manual) 12-11 Current output...
  • Page 37: Wiring

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 37 Wiring General wiring instructions  1. Wire only the sensor circuit into the potentially explosive atmosphere. 2. The installation of the Pt100 sensor circuit in the Ex Zone must comply with the requirements for the applicable type of protection, such as: •...
  • Page 38: Wiring Example

    38 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) Wiring example  In this example, contacts of the Pt100 relay(s) are wired to digital input DI6 of the drive control unit. 1. Connect the Pt100 sensor(s) of the motor to the relay(s) K71.x, K72.x and K73.x (whichever are present) through terminal block [X506].
  • Page 39: Start-Up And Acceptance Test

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 39 Start-up and acceptance test You need the Drive composer PC tool or a control panel to perform the start-up and acceptance test. If you have to set FSO module parameters, you need the Drive composer pro PC tool. Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
  • Page 40: Maintenance

    40 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) Maintenance After the operation of the circuit has been verified at start-up, the circuit requires a proof test at least once in a year. If you change any wirings or components related to the motor thermal protection function after the start-up, repeat the procedure given in section Start-up and acceptance test above.
  • Page 41: Safety Data

    ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 41 Safety data The safety block diagrams show the components that are included in the safety data calculations. Without an FSO module  Extension Pt100 relay(s) Drive STO relay(s) Customer K71.1…3 motor Pt100 (K72.1…2) sensors...
  • Page 42 42 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
  • Page 43: Parameter Settings

    For more information, see the firmware manual. For Ex motors supplied by other motor manufacturers, contact the motor manufacturer for the correct value and your local ABB representative for instructions on how to make the parameter setting in the drive.
  • Page 44: Reset Method And Status Indications

    There are two ways to configure the motor overtemperature indication. Example 1 The ACS880 primary control program has two separate temperature monitoring functions. In this example, one of these functions (External event function 1) is configured to monitor digital input DI6 (you can also use another digital input). When off (0), the function triggers the user-selected indication and shows the user-defined message.
  • Page 45: 31.11 Fault Reset Selection

    Parameter settings 45 31.11 Fault reset selection Select the correct source of an external fault reset signal with parameter 31.11 Fault reset selection. Other recommended settings  We recommend that you also set these parameters to improve the safety of the application: •...
  • Page 46: Fso Module

    (SS1 function in the FSO module, stop category 1). For the options described in this manual, ABB has configured the FSO module so that it activates the STO function (stop category 0). Always consider which stop category is more appropriate for the motor in overtemperature situations.
  • Page 47 SS1 function: The FSO module activates drive STO function when the drive has decelerated the motor speed below this value. Adjust the default value when necessary. ACS880-07/17/37 drives with the option +Q978: Also the main contactor/breaker is opened. FSOGEN.52 Zero speed with...
  • Page 48: Parameters For The Sto Function

    In the safety functions described in this manual, this parameter has value None. ACS880-07/17/37 drives with the option +Q978 or +Q979: ABB has connected the emergency stop button to this digital input at the factory. Make sure that the setting corresponds to the circuit diagrams of the delivery.
  • Page 49 In the safety functions described in this manual, this feature is not used and this parameter has value None. ACS880-07/17/37 drives with the option +Q978: The SBC function is used in the emergency stop implementation to control the auxiliary safety relay(s) which is connected to the main contactor/breaker.
  • Page 50: Parameters For The Sse Function

    STO function. SAR0 parameters define the deceleration ramp (for more information, see the FSO module user’s manual). For the safety functions described in this manual, ABB has set this parameter to value Immediate STO at the factory. Adjust the default value when necessary.
  • Page 51 Parameter settings 51 Index Name Example Description value SS1.14 SS1 delay for STO 20000 ms Sets the security delay after which the FSO module activates the drive STO and SBC at the latest, if the motor speed has not gone below the zero speed limit (parameter FSOGEN.51 or FSOGEN.52) yet.
  • Page 52: Ss1 Ramp Parameters In The Drive/Inverter Unit

    52 Parameter settings In addition to the parameters related to the SS1 function, change or set the value of these parameters. Index Name Pre-set value Value with the SS1 function (STO function) STO.12 STO input B DI X113:4 None FSOGEN.51 Zero speed without 90 rpm If you do not use a safety encoder, adjust the encoder...
  • Page 53: Notes

    In motor overtemperature situations, the FSO module also opens the main contactor/ circuit breaker. ACS880-07/17/37 drives with the option +Q978 or +Q979 The FSO module is configured so that after the safety function activation, the user must reset the FSO module manually with the emergency stop reset button. In this case, the user must reset the FSO module with the emergency stop reset button also after motor overtemperature situations.
  • Page 54 54 Parameter settings...
  • Page 55: Technical Data

    Technical data 55 Technical data Contents of this chapter This chapter contains the technical specifications of the protection functions and the PTC and Pt100 relays. It also gives general rules, notes and definitions related to safety functions and lists related standards. The ATEX compliance markings and certificates are also included.
  • Page 56: Ptc Thermistor Relays

    56 Technical data PTC thermistor relays ABB CM-MSS.41  Ordering information Part number CM-MSS.41P (Push-in terminals): 1SVR740712R1200 CM-MSS.41S (Screw terminals): 1SVR730712R1200 Power supply A1-A2 (non-isolated) Rated voltage 24…240 V AC/DC Rated control supply voltage tolerance -15%…+10% Rated frequency 15…400 Hz Typical current/ power consumption 24 V AD/DC: 33 mA/ 0.55 VA...
  • Page 57 Technical data 57 Indication of operating states Control supply voltage “U” LED (green) Relay status “R” LED (yellow) Fault message “F” LED (red) Operating controls Test / Reset front-face button Configuration of DIP switch 1 non-volatile fault storage Configuration of DIP switch 2 short-circuit detection Output circuit Kind of output...
  • Page 58 Output circuit 1 / Output circuit 2 no Pollution degree (IEC/EN 60664-1) Overvoltage category (IEC/EN 60664-1) Potential of measuring circuit = Potential of control circuit More information, see Thermistor motor protection relay CM-MSS.41 Data sheet (2CDC112216D0201 [English]) in the ABB Library.
  • Page 59 Technical data 59 DOLD MK 9163N.12/110-ATEX  Ordering information Part number 0056901 Power supply A1-A2 (non-isolated) Rated voltage 24 V AC/DC Voltage range AC 0.8…1.1 U at 10% residual ripple: DC 0.9…1.25 U at 48% residual ripple: DC 0.8…1.1 U Frequency 45…65 Hz Power consumption...
  • Page 60 Pt100 relays GM International D1073S  Ordering information Model D1073S Programming tool (not included in the ABB delivery) GM Pocket Portable Configurator PPC1090 RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator software (recommended) Power supply (terminals 3-4) Rated voltage...
  • Page 61 Technical data 61 Performance Reference conditions 24 V supply, 250 ohm load, 23 ± 1 °C ambient temperature Input: • Calibration and linearity accuracy < ± 40 microV on mV, 200 mohm on RTD or ± 0.05% of input value •...
  • Page 62 62 Technical data PRelectronics 9116B1 universal converter  Ordering information Universal converter - Uo 28 V DC (max. loop voltage) 9116B1 Display / Programming front (Not included in the ABB 4501 delivery) Power supply (terminals 32-31) Rated voltage 24 V DC Voltage range 19.2…31.2 V DC...
  • Page 63 Technical data 63 Terminals Wire size (max…min) AWG 26…14 / 0.13…2.08 mm stranded wire Dimensions Without 4501, Height × width × depth 109 × 23.5 × 104 mm With 4501, Height × width × depth 109 × 23.5 × 116 mm Approvals ATEX Ex II (1) G D IECEx...
  • Page 64: Competence

    64 Technical data General rules, notes and definitions Validation of the safety functions  You must do an acceptance test (validation) to validate the correct operation of safety functions. Validation procedure You must do the acceptance test using the checklist given in sections Start-up and acceptance test: •...
  • Page 65: Reporting Problems And Failures Related To Safety Functions

    Technical data 65 Reporting problems and failures related to safety functions  Contact your local ABB representative. Related standards and directives The ATEX-certified motor thermal protection functions comply with the standards listed below. Standard / Directive Name EN 50495: 2010...
  • Page 66: Atex Certificate

    66 Technical data ATEX Certificate...
  • Page 67 Technical data 67...
  • Page 68 68 Technical data...
  • Page 69: Declaration Of Conformity

    Technical data 69 Declaration of Conformity...
  • Page 70 70 Technical data Note: If the Declaration of Conformity is needed in any other official language of European Union than in English, contact ABB.
  • Page 71: Circuit Diagrams

    Circuit diagrams 71 Circuit diagrams Contents of this chapter This chapter contains circuit diagram examples illustrating the operation of the ATEX- certified motor thermal protection functions. For the actual configuration, see the circuit diagrams delivered with the drive.
  • Page 72 72 Circuit diagrams...
  • Page 73: 2L513+Q971 (Ptc Monitoring With Two Relays)

    +2L513+Q971 (PTC monitoring with two relays)
  • Page 74: 2L513+Q971+Q973 (Ptc Monitoring With Two Relays And Fso Module) - Sheet

    +2L513+Q971+Q973 (PTC monitoring with two relays and FSO module) – Sheet 60...
  • Page 75 +2L513+Q971+Q973 (PTC monitoring with two relays and FSO module) – Sheet 70...
  • Page 76: 5L514+Q971+Q973 (Pt100 Monitoring With Five Relays And Fso Module) - Sheet 60

    +5L514+Q971+Q973 (Pt100 monitoring with five relays and FSO module) – Sheet 60 =-A41 ZCU-12 CONTROL UNIT +01.1 -X12 =-A68 -X110 -X111 FSO-XX SAFETY OPTION, ADVANCED POWER STATUS/ FAULT =-X68B SAFETY CIRCUIT GENERATED FROM SOLUTION REVISION 5 RULES CONVERTED 26.9.2014 26.9.2014 Circuit diagram EFS2 Generated by ADG2 ABB Drives...
  • Page 77: 5L514+Q971+Q973 (Pt100 Monitoring With Five Relays And Fso Module) - Sheet 70

    Ex manager. Also notified body (VTT Expert Services Ltd.) must =-X35B =-X37B approve the change. (See instructions 3AFE002084 and 3AFE003559) =-X35A =-X37 SAFETY CIRCUIT 26.9.2014 PT100 ATEX temperature monitoring Circuit diagram EFS2 Generated by ADG2 ACS880-07 SINGLE DRIVE ABB Drives...
  • Page 79: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to abb.com/searchchannels.
  • Page 80 © Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice.