60 Technical data
Isolation data
Note: The supply and measurement circuits are not electrically isolated. Use a dedicated power supply for
the PTC relay(s).
Rated impulse withstand voltage between all isolated
circuits
Pollution degree
Overvoltage category
More information on the relay is available at www.dold.com.
Pt100 relays
GM International D1073S
Ordering information
Model
Programming tool (not included in the ABB delivery)
Power supply (terminals 3-4)
Rated voltage
Voltage range
Power consumption
Measuring circuit (terminals 13-16)
Sensor type
Integration time
Resolution
Visualization
Input range
Measuring RTD current
RTD line resistance compensation
RTD line resistance error compensation
Current output (terminals 1-2)
Signal range (span)
Resolution
Transfer characteristic
Response time
Output ripple
Output contacts (terminals 5-8)
Number of contacts
Hysterisis
ON-OFF delay time
Rated switching current
4 kV (EN 60664-1)
2
III
D1073S
GM Pocket Portable Configurator PPC1090
or
RS-232 serial line with PPC1092 Adapter and
SWC1090 Configurator software (recommended)
24 V DC (reverse polarity protected)
20...30 V DC
< 2.1 W at 30 V supply voltage, overload condition,
relays energized and PPC1090 connected
3-4 wire RTD Pt100 (For other alternatives, refer to
www.gminternationalsrl.com.)
500 ms
20 microV
0.1 °C on temperature
10 microV on mV
0.1% on potentiometer
Within rated limits of sensor (-10...+ 80 mV)
< 0.5 mA
< 10 ohm
-5...+20 ohm, programmable
0/4 to 20 mA, on max. 600 ohm load source mode,
current limited at 22 mA
2 microA current output
Linear or reverse
< 50 ms (10...90% step change)
< 20 mVrms on 250 ohm load
Two SPST relay contacts
Programmable
0...1000 s, 100 ms step, separate setting
2 A / 250 V AC / 500 VA
2 A / 250 V DC / 80 W (resistive load)