3. SPECIFICATIONS
3.5

Data Link Processing Time

Downloaded from
ManualsNet.com
For the AJ65BT-68TD, the data link processing time shown below will be required in order to execute
each function.
For details on link scan time, refer to the AJ61BT11/A1SJ61BT11 CC-Link System Master/Local
Module User's Manual or the AJ61QBT11/A1SJ61QBT11 CC-Link System Master/Local Module
User's Manual.
(1) Mater station (RY) → Remote device station (RY) processing time
[Expression]
SM + LS × 3 + Remote device station processing time (90 ms) [ms]
SM : Master station sequence program scan time
LS : Link scan time
(2) Master station (RWw) → Remote device station (RWw) processing time
[Expression]
SM + LS × 3 + Remote device station processing time (90 ms) [ms]
SM : Master station sequence program scan time
LS : Link scan time
(3) Master station (RX) ← Remote Device Station (RX) Processing Time
[Expression]
SM + LS × 2 + Remote device station processing time (1 ms) [ms]
SM : Master station sequence program scan time
LS : Link scan time
(4) Master station (RWr) ← Remote Device Station (RWr) Processing Time
[Expression]
SM + LS × 2 + Remote device station processing time (1 ms) [ms]
SM : Master station sequence program scan time
LS : Link scan time
POINT
The above are examples of processing time until the control of the output signal to the AJ65BT-
68TD from the programmable controller CPU or until input signals or remote registers are read.
The maximum time that takes for updating the detected temperature read by the programmable
controller CPU is "data link processing time + sampling time."
search engine
AJ65BT-68TD
AJ65BT-68TD
AJ65BT-68TD
AJ65BT-68TD
3-5
MELSEC-A