3. SPECIFICATIONS
3.9

Remote Register

Downloaded from
ManualsNet.com
The AJ65BT-68TD is equipped with remote registers for data communication with the master module.
The assignment and data structure of the remote register are explained below.
3.9.1

Remote register assignment

The remote register assignments are shown in the table below.
Communication
Address
direction
RWwm
RWwm+1
RWwm+2
RWwm+3
RWwm+4
RWwm+5
RWwm+6
Master
RWwm+7
RWwm+8
Remote
RWwm+9
RWwm+10
RWwm+11
RWwm+12
RWwm+13
RWwm+14
RWwm+15
RWrn
RWrn+1
RWrn+2
RWrn+3
RWrn+4
RWrn+5
RWrn+6
Remote
RWrn+7
RWrn+8
Master
RWrn+9
RWrn+10
RWrn+11
RWrn+12
RWrn+13
RWrn+14
RWrn+15
search engine
Description
CH. 1 lower limit value (0.1 °C units)
CH. 1 upper limit value (0.1 °C units)
CH. 2 lower limit value (0.1 °C units)
CH. 2 upper limit value (0.1 °C units)
CH. 3 lower limit value (0.1 °C units)
CH. 3 upper limit value (0.1 °C units)
CH. 4 lower limit value (0.1 °C units)
CH. 4 upper limit value (0.1 °C units)
CH. 5 lower limit value (0.1 °C units)
CH. 5 upper limit value (0.1 °C units)
CH. 6 lower limit value (0.1 °C units)
CH. 6 upper limit value (0.1 °C units)
CH. 7 lower limit value (0.1 °C iunits)
CH. 7 upper limit value (0.1 °C units)
CH. 8 lower limit value (0.1 °C units)
CH. 8 upper limit value (0.1 °C units)
CH. 1 detected temperature value(0.1 °C units)
CH. 2 detected temperature value(0.1 °C units)
CH. 3 detected temperature value(0.1 °C units)
CH. 4 detected temperature value(0.1 °C units)
CH. 5 detected temperature value(0.1 °C units)
CH. 6 detected temperature value(0.1 °C units)
CH. 7 detected temperature value(0.1 °C units)
CH. 8 detected temperature value(0.1 °C units)
CH. 1 scaling value
CH. 2 scaling value
CH. 3 scaling value
CH. 4 scaling value
CH. 5 scaling value
CH. 6 scaling value
CH. 7 scaling value
CH. 8 scaling value
m,n : Address assigned to the master module by the station number setting
3-22
MELSEC-A
Reference
Default value
section
Measured
temperature
range for the
Section
currently
3.9.2
selected
thermocouple
Section
3.9.3
0
Section
3.9.4