4. SETTING AND PROCEDURE BEFORE OPERATION
Downloaded from
ManualsNet.com
4.4.2
Error compensation procedure
The following shows the flow of error compensation.
Start
Set the mode switch to 9 for test mode.
After two seconds, confirm that the RUN LED is
turned off.
RUN
Turns off
8
after 2
7
seconds
B
Select the channel to compensate using the mode
switch.
MODE
Turn the knob
0 1
9
to the channel
8
2
to be set.
7
3
6
4
5
Input a value to be the offset value.
AJ65BT-68TD
Set the offset/gain setting switch at OFFSET.
OFFSET
RUN
Flickers at
0.5 second
intervals
Adjust the detected temperature value to the offset
value using the UP/DOWN switch.
AJ65BT-68TD
-497
The offset value is memorized by switching the
offset/gain setting switch to SET.
OFFSET
RUN
Off
A
POINT
Once an offset value or gain value is set in the test mode, the set value cannot be confirmed (the
set value is retained in the internal memory.)
search engine
MODE
0 1
9
2
3
6
4
5
-50 [°C]
SET
GAIN
NO
B
UP
500
DOWN
SET
GAIN
4-7
A
Input a value to be the gain value.
AJ65BT-68TD
Set the offset/gain setting switch at GAIN.
OFFSET
RUN
Flickers at
0.5 second
intervals
GAIN
Adjust the detected temperature value to the gain
value using the UP/DOWN switch.
AJ65BT-68TD
797
The gain value is memorized by switching the offset/gain
setting switch to SET.
OFFSET
RUN
Off
GAIN
Is compensation completed
for the channel used?
YES
Set the mode switch to 0 and return to the normal
mode.
RUN
MODE
9
Turns on
8
after 2
7
seconds
6
End
MELSEC-A
80 [°C]
SET
UP
800
DOWN
SET
0 1
2
3
4
5