3. SPECIFICATIONS
Signal direction : AJ65BT-68TD
Device No.
RX (n+5) 0
RX (n+5) 1
RX (n+5) 2
RX (n+5) 3
RX (n+5) 4
RX (n+5) 5
RX (n+5) 6
RX (n+5) 7
RX (n+5) 8
to
RX (n+7) 6
RX (n+7) 7
RX (n+7) 8
RX (n+7) 9
RX (n+7) A
RX (n+7) B
RX (n+7) C
to
RX (n+7) F
Downloaded from
ManualsNet.com
Master module
Signal name
Use prohibited
Initial data processing request flag
Initial data setting completion flag
Error status flag
Remote READY
Use prohibited
n : Addresses assigned to the master module by the station number setting.
POINT
Do not turn on the output signals that are prohibited in respect to the remote device from the
master module.
If the prohibited signals are output, the programmable controller system may malfunction.
search engine
Signal direction : Master module
Device No.
RY (n+5) 0
All CH. batch type "K" thermocouple selection flag
RY (n+5) 1
All CH. batch type "E" thermocouple selection flag
RY (n+5) 2
All CH. batch type "J" thermocouple selection flag
RY (n+5) 3
All CH. batch type "T" thermocouple selection flag
RY (n+5) 4
All CH. batch type "B" thermocouple selection flag
RY (n+5) 5
All CH. batch type "R" thermocouple selection flag
RY (n+5) 6
All CH. batch type "S" thermocouple selection flag
RY (n+5) 7
Pt100 cold junction compensation disable flag
RY (n+5) 8
to
RY (n+7) 6
RY (n+7) 7
Offset/gain value selection flag
RY (n+7) 8
Initial data processing completion flag
RY (n+7) 9
Initial data setting request flag
RY (n+7) A
RY (n+7) B
RY (n+7) C
to
RY (n+7) F
3-10