Name
AlarmPriority_HumSens
Alarm_SylkCommFailure
Alerts
Table 8 Alerts (Continued)
BACnet
BACnet
Object
Object
Type
Instance
Analog
2082
Value
Multistate
2036
Value
Range
{BIT0=INACTIVE,
BIT1=HIGH,
BIT2=MEDIUMN_ONBOARD,
BIT4=MEDIUMN_SYLK}
enum{Normal=1,
SylkAddr2Fail=2,
SylkAddr3Fail=3,
SylkAddr4Fail=4,
SylkAddr5Fail=5,
SylkAddr10Fail=10,
ManySylkFail=16}
Description
High Priority:
1. Only local sensor
configured & on-board
humidity sensor is in
alarm
2. Only Remote sensor
configured & TR40 sensor
connected to Sylk address
2 is giving null value and
digital output is
configured for
Humidification and
Dehumidification.
3. Configured as multi
sensor & both the remote
sensor & on-board
configured sensor has
failed.
Medium priority:
1. Configured as Multi
sensor & only the on-
board sensor has failed.
but getting reliable value
from the sylk sensors.
2. Configured as multi
sensor & only the sylk
sensor has failed with
values available from on-
board sensor.
When a valid network
humidity is available, then
the high priority alarms
will be considered as
medium priority alarm.
Sylk communication
failure alarm. If more than
one Sylk sensor has failed,
then 'ManySylkFail' alarm
would be generated &
installer has to check the
BACnet points related to
all Sylk sensors to
understand which sensor
has failed.
37