hit counter script

Honeywell TC300 Integration Manual page 50

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Name
Cfg_FanCoilManualSpeedSel
Cfg_FanConfig
50
Table 17 Fan configuration (Continued)
BACnet
BACnet
Object
Object
Type
Instance
Multistate
583
Value
Analog
2087
Value
Default
Range
Value
1
enum{Auto=1,
Low=2,
Medium=3,
High=4,
Off=5,
Circulate=6}
15
{BIT1=Auto,
BIT2=Manual,
BIT3=Circulate}
Description
Fan speed
Fan
configuration.
BIT1 Auto
must be set as
1, manual and
circulate can
be set as 1 or
0.
Fan configuration

Advertisement

Table of Contents
loading