Name
Cfg_PipeTempCoolThreshold
Cfg_PipeTempHighLimit
Cfg_PipeTempLowLimit
Cfg_PipeSpaceHeatTempOffset
Cfg_PipeSpaceCoolTempOffset
Indoor temperature limits
Table 24 Indoor temp limits
BACnet
BACnet
Object
Object
Type
Instance
Analog
2071
Value
Analog
2072
Value
Analog
2073
Value
Analog
2074
Value
Analog
2075
Value
Default
Range
Value
60 °F
45 to 65 °F
180 °F
70 to 220 °F
40 °F
30 to 60 °F
5 °F
5 to 10 °F
-5 °F
-10 to -5 °F
Description
Pipe sensor threshold for
cooling
Pipe temperature alarm
high limit
Pipe temperature alarm
low limit
2 pipe single coil hybrid
control space
temperature offset for
heating
2 pipe single coil hybrid
control space
temperature offset for
cooling