Network Inputs - Honeywell TC300 Integration Manual

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Network inputs

Name
ni_NetSchCurrentState
ni_NetSchNextState
ni_NetTUNCOS
ni_ApplicationMode
ni_BypassState
ni_OccupancySensorState
ni_ShutdownState
ni_SpaceRH
ni_SpaceTemp
ni_RunTimeReset
ni_DATemp
ni_PipeTempMode
Network inputs
Table 34 Network inputs
BACnet
BACnet
Object
Object
Type
Instance
Multistate
1
Value
Multistate
2
Value
Analog
1
Value
Multistate
3
Value
Binary
1
Value
Multistate
6
Value
Binary
4
Value
Analog
80
Value
Analog
104
Value
Multistate
38
Value
Analog
2024
Value
Multistate
2012
Value
Default
Range
Value
5
enum{Occupied=1,
Unoccupied=2,
Bypass=3,
Standby=4,
NoOverride=5}
5
enum{Occupied=1,
Unoccupied=2,
Bypass=3,
Standby=4,
NoOverride=5}
0 to 11520 minutes
1
enum{Auto=1,
Cool=2,
Heat=3,
FanOnly=4,
Off=5}
0
Disable=0,
Enable=1
5
enum{Occupied=1,
Unoccupied=2,
Bypass=3,
Standby=4,
NoOverride=5}
0
Normal=0,
Shutdown=1
0 to 100% RH
-40 to 150 °F
1
enum{
Normal=1,
FanReset=2,
CoolReset=3,
HeatingReset=4}
-40 to 200 °F
1
enum{
NoUse=1,
Cool=2,
Heat=3}
Description
Current schedule state
from network.
Next schedule state
from network.
TUNCOS is the
difference between
the future change in
event & current event
in minutes.
Effective application
mode from network.
This value will not be
persisted over a power
cycle.
Net bypass input to
enable bypass timer
Network occupancy
sensor state
System shutdown
input from network.
Space humidity
network input
Space temperature
network input
Runtime accumulate
reset network input.
Discharge air
temperature network
input
Pipe temperature
mode network input
71