Name
Cfg_FanCoilType
Cfg_FanCoilHtgType
Cfg_FanCoilClgType
Cfg_FanCoilHtgDriveTime
Cfg_FanCoilClgDriveTime
Cfg_FanCoilTwoPipeSingleCoil
Type
Cfg_FanCoilHtgDriveType
Cfg_FanCoilClgDriveType
Cfg_FanCoilHtgFloatingSyncE
n
Equipment
Table 21 Equipment (Continued)
BACnet
BACnet
Object
Object
Type
Instance
Multistate
575
Value
Multistate
576
Value
Multistate
577
Value
Analog
1721
Value
Analog
1722
Value
Multistate
580
Value
Multistate
578
Value
Multistate
579
Value
Binary
453
Value
Default
Range
Value
1
enum{4PipeDualCoil=1,
4PipesingleCoil=2,
PipeSingleCoil=3}
2
enum{None=1,
OnOff=2,
Floating=3,
Modulating=4}
2
enum{None=1,
OnOff=2,
Floating=3,
Modulating=4}
90
0 to 240 seconds
seconds
90
0 to 240 seconds
seconds
1
enum{Heat&Cool=1,
HeatingOnly=2,
CoolingOnly=3}
1
enum{Direct=1,
Reverse=2}
1
enum{Direct=1,
Reverse=2}
1
Disable=0,
Enable=1
Description
Fan coil type
4 pipe dual coil
heating valve
type, 4 pipe
single coil/
2 pipe single
coil valve type
4 pipe dual coil
cooling valve
type
4 pipe dual coil
floating
heating drive
time, 4 pipe
single coil/2
pipe single coil
valve drive
time
4 pipe dual coil
floating
cooling drive
time
2 pipe single
coil type
4 pipe dual coil
floating
heating drive
type, 4 pipe
single coil/2
pipe single coil
floating valve
drive type
4 pipe dual coil
floating
cooling drive
time
4 pipe dual coil
floating
heating sync
enable, 4 pipe
single coil/2
pipe single coil
floating valve
sync enable