Wall Module Configuration; Network - Honeywell TC300 Integration Manual

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Wall module configuration

Name
Cfg_Thermostat_SysSwitch
Cfg_Thermostat_BypOverrideTime
Cfg_Thermostat_TempOffSpLimit
Cfg_Thermostat_MinCoolSp
Cfg_Thermostat_MaxHeatSp
Cfg_Thermostat_SystemConfig
Cfg_Thermostat_Override
Cfg_TstatOverrideType

Network

Name
no_mstpHeaderCrcError
no_mstpDataCrcErr
ni_mstpClearErr
66
Table 32 Wall module configuration
BACnet
Object
Type
Multistate
Value
Analog
Value
Analog
Value
Analog
Value
Analog
Value
Analog
Value
Binary
Value
Multistate
Value
Table 33 Network
BACnet
BACnet
Object
Object Type
Instance
Analog Value
2005
Analog Value
2006
Binary Value
174
BACnet
Default
Object
Value
Instance
8
1
10
180
minutes
102
30 °F
12
50 °F
13
90 °F
2023
15
135
0
2035
2
Range
Unclear=0,
Clear=1
Range
enum{Auto=1,Co
The system switch
ol=2,
may be used by the
Heat=3,
contractor or
Ventilation=4,
occupant to change
Off=5}
the operation of the
unit.
0 to 1080
Unoccupied override
minutes
time
0 to 45 °F
This point is used to
limit the range of
user adjustable
setpoint.
50 to 99 °F
Minimum cool
setpoint of
thermostat
40 to 90 °F
Maximum heat
setpoint of
thermostat
{BIT0=Auto,
To limit available user
BIT1=Heat&Cool
configurable options.
BIT2=Ventilation
BIT 3 Off must be set
BIT3=Off}
as 1.
OverrideOff=0,O
Thermostat bypass
verrideOn=1
override
enum{
Thermostat override
Permanent=1,Te
type
mporary=2}
Description
The number of header CRC errors in
received frames
The number of data CRC errors in
received frames
Write to 1 and then 0 will clear header
CRC and data CRC count.
Wall module configuration