hit counter script

Cisco 6503 - Catalyst Firewall Security Sys Installation Manual page 278

Installation guide
Hide thumbs Also See for 6503 - Catalyst Firewall Security Sys:
Table of Contents

Advertisement

Removing and Installing the DC-Input Power Supplies
Note
Wire for 4500 W (right side of power supply bay) as follows:
Step 10
a.
From the right side of the power supply, connect the ground wire to the ground (see
Figure 4-52
Input power
module
From the right side of the power supply, connect each of the DC-input wires to the right power
b. \
supply terminal block (see
Note
Secure outer block cover.
c.
Catalyst 6500 Series Switches Installation Guide
4-72
For multiple DC input power supply, each DC input must be protected by dedicated circuit
breaker or fuse. The circuit breaker or fuse should be sized according to the power supply input
rating and local or national electrical code requirements.
DC-Input Wire Connections for 4000-W DC-Input Power Supply, Right Side of Power
Bay
Terminal
block cover
Power
CI SC O SY
ST EM S, IN
C
switch
Captive
installation
screw
Figure 4-47
Negative (-)
Positive (+)
When you tighten the terminal nuts, make sure they are snug. Do not over tighten them.
Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can
break the terminal block (Maximum torque: 36 inch-pounds).
Chapter 4
1
2
3
IN PU T
4
OK
FA N
OU TP UT
OK
FA IL
( ) Ground
and
Figure
4-52) in this order:
Removal and Replacement Procedures
Figure
4-52).
Power leads
attached to
terminal block
( - ) Negative
(+) Positive
( - ) Negative
(+) Positive
( - ) Negative
(+) Positive
OL-5781-08

Advertisement

Table of Contents
loading

This manual is also suitable for:

Catalyst 6500 series

Table of Contents