ABB ACS880 Firmware Manual page 155

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
33.30
Edge counter 1
actual
0...4294967295
33.31
Edge counter 1 limit
0...4294967295
33.32
Edge counter 1 func
Bit
Function
0
Counter mode
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds
1 = Saturate: If warning is enabled by bit 1, it stays active until reset
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning is given when the limit is reached
2
Count rising edges
0 = Disable: Rising edges are not counted
1 = Enable: Rising edges are counted
3
Count falling edges
0 = Disable: Falling edges are not counted
1 = Enable: Falling edges are counted
4...15
Reserved
0000h...FFFFh
33.33
Edge counter 1
source
False
True
RO1
Other [bit]
33.34
Edge counter 1
divider
1...4294967295
33.35
Edge counter 1
warning selection
Edge counter 1
Main contactor
Output relay
Motor starts
Power ups
Description
Reading of signal edge counter 1. Can be reset on the control
panel by keeping Reset depressed for over 3 seconds.
Reading of signal edge counter 1.
Sets the warning limit for signal edge counter 1.
Warning limit for signal edge counter 1.
Configures signal edge counter 1. This counter is
incremented every time the signal selected by parameter
33.33 Edge counter 1 source
depending on the setting of this parameter). A divisor may be
applied to the count (see
After the limit set by
33.31 Edge counter 1 limit
the warning specified by
selection
is given (if enabled by this parameter), and the
counter reset.
The current value of the counter is readable from parameter
33.30 Edge counter 1
actual. Bit 2 of
indicates that the count has exceeded the limit.
Edge counter 1 configuration word.
Selects the signal to be monitored by signal edge counter 1.
Constant 0.
Constant 1.
Bit 0 of
10.21 RO status
Source selection (see
Terms and abbreviations
Divisor for signal edge counter 1. Determines how many
signal edges increment the counter by 1.
Divisor for signal edge counter 1.
Selects the warning message for signal edge counter 1.
Pre-selectable warning message for signal edge counter 1.
Pre-selectable warning message for signal edge counter 1.
Pre-selectable warning message for signal edge counter 1.
Pre-selectable warning message for signal edge counter 1.
Pre-selectable warning message for signal edge counter 1.
switches on or off (or either,
33.34 Edge counter 1
divider).
is reached,
33.35 Edge counter 1 warning
33.01 Counter status
(page 86).
on page 73).
Parameters 155
Def/FbEq16
-
-
0
-
0000b
1 = 1
False
0
1
2
-
1
-
Edge counter
1
2
11
12
13
14