hit counter script

Cisco Vg310 And Cisco Vg320 Voice Gateways Hardware Installation Guide - Cisco VG310 Hardware Installation Manual

Voice gateway
Hide thumbs Also See for VG310:
Table of Contents

Advertisement

Installing the Cisco VG310 and Cisco VG320 Voice Gateways
Warning
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
recommended ambient temperature of: 40 °C (104 °F). Statement 1047
If installed on enclosed racks, the racks must have adequate ventilation. An enclosed rack should never
Caution
be overcrowded and should have louvers and a fan.
If the Cisco VG310 or Cisco VG320 is installed in an enclosed rack with a ventilation fan at the top, make
sure that heated air drawn upward from other equipment does not pass through the Cisco VG310 or Cisco
VG320 chassis.
If the chassis is installed using slide rails, check for blocked ventilation ports when it is in position in the rack
or cabinet. Make sure that the ventilation ports of the chassis are not blocked.
Tip
Baffles can help isolate exhaust air from intake air. Baffles also help draw cooling air through the cabinet.
The best location for the baffles depends on the airflow patterns in the rack. You can test the airflow by
experimenting with different equipment arrangements.
Machine screws for securing the chassis in a rack are not included in the package. You must arrange for
Note
machine screws of the appropriate size required by your rack.
Procedure
Step 1
Attach the long leg of the mounting brackets to the chassis.
Figure 7: Attaching the Brackets to a Chassis (For 19-Inch Rack)
Figure 8: Attaching the Brackets to a Chassis (For Telco 19-Inch Rack)
OL-31292-01

Cisco VG310 and Cisco VG320 Voice Gateways Hardware Installation Guide

Mounting the Chassis on a Rack
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vg320

Table of Contents