hit counter script

Siemens SIMATIC S7 System Manual page 467

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Table 8- 22
Using Freeport mode
Network configuration
Using Freeport over an
RS232 connection
Using USS protocol
Creating a user program
that emulates a slave
device on another net-
work
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
Description
Example: Using an S7-200 SMART CPU with an
electronic scale that has an RS232 port.
Connect the two devices using one of the follow-
ing methods:
RS232/PPI Multi-Master cable connects the
RS232 port on the scale to the RS485 port
on the CPU. (Set the cable to PPI/Freeport
mode, switch 5 = 0.)
Using the CM01 signal board (SB) (S CPUs
only) which supports RS232 and RS485, you
can connect the RS232 device directly to the
CPU SB RS232 without using the RS232/PPI
cable.
CPU uses Freeport to communicate with the
scale.
Baud rate can be from 1.200 Kbps to
115.2 Kbps.
User program defines the protocol.
Example: Using an S7-200 SMART CPU with
SIMODRIVE MicroMaster drives.
STEP 7-Micro/WIN SMART provides a USS
library.
The CPU is a master, and the drives are slaves.
Example: Connecting S7-200 SMART CPUs to a
Modbus network.
User program in the CPU emulates a Modbus
slave.
STEP 7-Micro/WIN SMART provides a Modbus
library.
Communication
8.6 RS485
467

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents

Save PDF