Operational Indications and Operating Parameters
15.2 Basic Functions
Parameter
Scan cycle for indications
Response timeout
Retry limit
Scan cycle on error
Buttons:
Import
Export
Measured values 1-8 and 9-15
Indications
352
Default Setting
0 (*10 ms)
10 (*10 ms)
2
5 s
Inactive
Setting Range
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = Each interrogation cycle
Minimum time difference between the meas-
ured-value requests
1 to 6000 * 10 ms
(10 ms to 60 s)
0 to 10
(0 = No request retries)
Number of request retries after expiration of
Response timeout before a communication
error for the Modbus slave is identified.
1 to 3600 s
(1 s to 1 h)
Retry cycle for sending request telegrams if the
retry limits are exceeded or in the case of error
responses.
The buttons in the Mapping columns are only
activated if the option Activated = yes has been
set. The functions of the buttons are described
in the following chapters.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021