hit counter script

Siemens SICAM Q100 7KG95 Series Manual page 353

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Table 15-13
Parameter
Name
Unit
Note on frequency measured
values:
If a frequency measured value
(unit: Hz) has been parameter-
ized without a multiplier (multi-
plier: -), an additional check is
made whether the resulting
value is in the range of 15 Hz to
65 Hz. Measured values outside
this range are marked as
invalid.
Factors
Selecting a multipier for the
following units is not recom-
mended and will be rejected:
-none-
°
°C
°F
%
Register type
Data format on bus
Register number
Scaling factor
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Settings for Assignment of the Measured Values of the Modbus Slave Device 1
Default Setting
MV x Slv 1
(Measured Value of
connected Slave device 1;
x = 1 to 15)
Multiplier: –
Unit: -none-
-none-
Float32 (2 registers)
1
1.000
Operational Indications and Operating Parameters
Setting Range
Max. 31 characters
Max. 10 characters if the name is also to be
displayed on the device display.
m (milli)
c (centi)
d (deci)
h (hecto)
k (kilo)
M (Mega)
G (Giga)
-none-
m
kg
s
A
°C
V
Hz
W
Pa
m2
m3
VA
var
°
Wh
VAh
varh
%
°F
-none-
Input registers
Holding registers
For -none-, the assignment is ignored and the
corresponding measured value cannot be
selected for other functions.
Float32 (2 registers)
Int16 (1 register)
Int16_Ung8000h (1 register)
UInt16 (1 register)
UInt32 (2 registers)
1 to 65 535
Any float value
0.00: resulting measured value = 0.00
15.2 Basic Functions
353

Advertisement

Table of Contents
loading

Table of Contents