hit counter script

Advanced Functions; Process Connections; Binary Inputs; Binary Outputs - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Operational Indications and Operating Parameters

15.3 Advanced Functions

15.3
Advanced Functions

Process Connections

15.3.1
15.3.1.1

Binary Inputs

Table 15-17
Parameter
Threshold voltage
Threshold voltage
(one setting for both binary
inputs)
Binary inputs
60
Routed as:
Software filtering time
(only settable if Routed as: is
set to Status information)
Source inverted
Add entry to operational log
(only settable if Routed as: is
set to Status information)
Binary input indication
15.3.1.2

Binary Outputs

Table 15-18
Parameter
Source type
Source Type Indication
62
Indication
Source inverted
(can be set individually for all
relay outputs)
Operating mode
(can be set individually for all
relay outputs)
60
The parameter cannot be changed in this field. In the Configuration tab, Energy management menu, select Load profile source or
Tariff source. If you did not select a source, Status information is automatically selected.
31 bytes of UTF-8
61
If you select -none- as the source of an indication or energy counter, the corresponding binary output is inactive.
62
63
If you have selected one of the 2 Pulse types in the Operating mode list box, enter an output time x (in x *10 ms) in the Output
time for pulse operating mode field.
356
Settings for Binary Inputs U1/U2 and U3/U2
Default Setting
19 V
Status information
1 (* 2 ms)
no
yes
For example for terminal
U3/2:
Binary Input 2
Settings for Binary Outputs
Default Setting
Indication
-none-
No
Persistent
63
Setting Range
19 V
88 V
176 V
Status information
Load profile source
Tariff source
2 ms to 120 000 ms
(settable in 2-ms increments)
no
yes
no
yes
61
Max. 31 characters
Setting Range
Indication
Energy counter
Acc. to list box
No
Yes
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021

Advertisement

Table of Contents
loading

Table of Contents