Figure 2-40
Table 2-27
Label
MT
DS
RN
RT
OF
FM
SC
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Resulting CLIENT MAPPING INFORMATION (Example)
Description and Setting Ranges of the Parameters in the Text File
Measurand (MV)
Indication (I)
MV
MV, I
MV, I
MV, I
I
MV, I
MV
Description
Mapping Type
(Data type)
Description
Name of the associated data
object
Register number
(within the selected register
type RT)
Register type
Bit offset
(for INDICATION in Holding
registers)
Data format
Scaling factor for MEASURAND
Basic Functions
2.6 Serial Communication
Setting Range
MEASURAND
INDICATION
String with max. 31 characters
Longer strings are cut at
31 characters during import.
1 to 65 535
0x0 – Coil status register
0x1 – Input status register
0x3 – Input register
0x4 – Holding register
0 to 15 (for FT = 1BIT)
0 to 31 (for FM = 1BITI-
NUINT32)
For MEASURAND:
FLT32, INT16, UINT16, UINT32,
INT16INV7FFF and
INT16INV8000
For INDICATION:
1BIT, 1BITINUINT32
Arbitrary float value
81