Measuring and Recording
3.2 Measurement and Evaluation Functions
Recording and Evaluation
Table 3-9
Measured Quantity
(x = 1 to 50,
y = 1 to 49)
x = 1: Fundamental
Magnitude of Voltage Harmonics
H_Va-x
H_Vb-x
H_Vc-x
H_Vab-x
H_Vbc-x
H_Vca-x
Magnitude of Voltage Interharmonics
HI_Va-y
HI_Vb-y
HI_Vc-y
HI_Vab-y
HI_Vbc-y
HI_Vca-y
Magnitude of Current Harmonics
H_Ia-x
H_Ib-x
H_Ic-x
Magnitude of Current Interharmonics
HI_Ia-y
HI_Ib-y
HI_Ic-y
THDS, Voltage
THDS_Va
THDS_Vb
THDS_Vc
THDS_Vab
THDS_Vbc
THDS_Vca
THDS, Current
THDS_Ia
THDS_Ib
THDS_Ic
Interfaces: protocols IEC 61850 (PQDIF depending on the measuring interval) and Modbus
Configuration and Value View via the User Interface
3.2.2.2
Configuration of the Harmonics
The required settings for gathering the harmonics, interharmonics, and THDS are set in the main settings (see
chapter
2.4.1 Configuration via the User
tion and Value View via the User
106
Recording and Evaluation of the Harmonics/Interharmonics
Measurement Recorder
AVG
PQDIF, CSV
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Interface) and in the recorder settings (see chapter
Interface).
Measurement Recorder
Max. Value
PQDIF, CSV
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Measurement Recorder
Min. Value
PQDIF, CSV
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
x
x
x
x
x
x
x
x
x
7.8.2 Configura-