ONLINE MODULE CHANGE
(4) Operation check
7.3.5 When user range setting is used and initial setting was made with sequence program (other system is
(a) To make an operation check, click the [Cancel] button to cancel control
resumption.
(b) Click the [OK] button to leave the "Online module change" mode.
(c) Click the [Close] button to close the System Monitor dialog box.
(d) Enable the channels to be used in D/A conversion enable/disable setting (Un\G0).
Set digital values to CH
condition setting request (Y9) from off to on. Turn on Output enable/disable flag
(Y1 to Y6) of the used channel to check whether proper conversion has been
made or not.
(Be careful since corresponding analog signals will be actually output.)
Digital value (Un\G1 to Un\G6) and turn Operating
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 29