12.3 Point-to-Point (PtP) communication
You can set up the initial static configuration of the port in the device configuration
properties, or just use the default values. You can execute the SEND_CFG instruction in
your program to change the configuration.
The SEND_CFG configuration changes are not permanently stored in the CPU. The
parameters configured in the device configuration are restored when the CPU transitions
from RUN to STOP mode and after a power cycle. See Configuring transmit (send)
parameters (Page 552).
Table 12- 11 Data types for the parameters
Parameter and type
REQ
IN
PORT
IN
RTSONDLY
IN
RTSOFFDLY
IN
BREAK
IN
IDLELINE
IN
DONE
OUT
ERROR
OUT
STATUS
OUT
Table 12- 12 Condition codes
STATUS (W#16#....)
80B0
80B1
80B2
536
Data type
Description
Bool
Activate the configuration change on the rising edge of this input.. (Default
value: False)
PORT
After you install and configure a CM or CB communication device, the port
identifier appears in the parameter helper drop-list available at the PORT
box connection. The assigned CM or CB port value is the device
configuration property "hardware identifier". The port symbolic name is
assigned in the "System constants" tab of the PLC tag table. (Default value:
0)
UInt
Number of milliseconds to wait after enabling RTS before any Tx data
transmission occurs. This parameter is only valid when hardware flow
control is enabled. The valid range is 0 - 65535 ms. A value of 0 disables
the feature. (Default value: 0)
UInt
Number of milliseconds to wait after the Tx data transmission occurs before
RTS is disabled: This parameter is only valid when hardware flow control is
enabled. The valid range is 0 - 65535 ms. A value of 0 disables the feature.
(Default value: 0)
UInt
This parameter specifies that a break will be sent upon the start of each
message for the specified number of bit times. The maximum is 65535 bit
times up to an eight second maximum. A value of 0 disables the feature.
(Default value: 12)
UInt
This parameter specifies that the line will remain idle for the specified
number of bit times before the start of each message. The maximum is
65535 bit times up to an eight second maximum. A value of 0 disables the
feature. (Default value: 12)
Bool
TRUE for one execution after the last request was completed with no error
Bool
TRUE for one execution after the last request was completed with an error
Word
Execution condition code (Default value: 0)
Description
Transmit interrupt configuration is not allowed. Contact customer suport.
Break time is greater than the maximum allowed value.
Idle time is greater than the maximum allowed value.