553BTechnical specifications
A.4 CPU 1214C
Technical data
Smoothing
Noise rejection
Impedance
Isolation (field side to logic)
Accuracy (25°C / 0 to 55°C)
Cable length (meters)
A.4.3.1

Step response of the built-in analog inputs of the CPU

Table A- 50
Step Response (ms), 0V to 10V measured at 95%
Smoothing selection (sample averaging)
None (1 cycle): No averaging
Weak (4 cycles): 4 samples
Medium (16 cycles): 16 samples
Strong (32 cycles): 32 samples
Sample time
A.4.3.2

Sample time for the built-in analog ports of the CPU

Table A- 51
Sample time for built-in analog inputs of the CPU
Rejection frequency(Integration time selection)
60 Hz(16.6 ms)
50 Hz (20 ms)
10 Hz (100 ms)
686
Description
None, Weak, Medium, or Strong
See the table for step response (ms) for the analog inputs of the CPU
(Page 686).
10, 50, or 60 Hz
≥100 KΩ
None
3.0% / 3.5% of full-scale
100 m, shielded twisted pair
Rejection frequency (Integration time)
60 Hz
63 ms
84 ms
221 ms
424 ms
4.17 ms
50 Hz
65 ms
93 ms
258 ms
499 ms
5 ms
Sample time
4.17 ms
5 ms
25 ms
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
10 Hz
130 ms
340 ms
1210 ms
2410 ms
25 ms