Advertisement

12.5.2.5

MB_CLIENT example 2: Multiple requests with different TCP connections

Modbus client requests can be sent over different connections. To accomplish this, different
instance DBs, IP addresses, and connection IDs must be used.
The port number must be different if the connections are established to the same Modbus
server. If the connections are on different servers, there is no port number restriction.
The example shows both clients writing to the same memory area. Also, a returned error is
captured which is optional.
Network 1:
Modbus function 4 - Read input words (in S7-1200 memory)
Network 2:
Modbus function 3 - Read holding register words (in S7-1200 memory)
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
105BCommunication processor
12.5 Modbus communication
597