No.
Name / Range /
Selection
Abs low
Abs high
Both
Abs both
32.16
Supervision 2 action
No action
Warning
Fault
Fault if running
32.17
Supervision 2 signal
32.18
Supervision 2 filter
time
0.000 ... 30.000 s
32.19
Supervision 2 low
-21474830.00 ...
21474830.00
32.20
Supervision 2 high
-21474830.00 ...
21474830.00
32.25
Supervision 3 function
Disabled
Low
High
Abs low
Description
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit
or rises above its high limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
Selects the action the drive takes when the value monitored
by signal supervision 2 exceeds its limits.
Note: This parameter does not affect the status indicated
by
32.1 Supervision
status.
No action taken.
A warning
(A8B1 Signal supervision
The drive trips on
80B1 Signal supervision
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 2.
For the available selections, see parameter
Supervision 1
signal.
Defines a filter time constant for the signal monitored by
signal supervision 2.
Signal filter time.
Defines the lower limit for signal supervision 2.
Low limit.
Defines the upper limit for signal supervision 2.
Upper limit.
Selects the mode of signal supervision function 3.
Determines how the monitored signal (see parameter
32.27) is compared to its lower and upper limits
32.30
respectively).
The action to be taken when the condition is fulfilled is
selected by 32.26.
Signal supervision 3 not in use.
Action is taken whenever the signal falls below its lower
limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
2) is generated.
2.
80B1 Signal supervision
32.7
(32.29
Parameters 343
Def / Type
FbEq 16b / 32b
3
4
5
6
No action / uint16
0
1
2
2.
3
Zero / uint32
0.000 s / real32
1000 = 1 s / 1000 = 1
s
0.00 / real32
- / -
0.00 / real32
- / -
Disabled / uint16
and
0
1
2
3