(b) From the master station (RY) to a CC-Link remote I/O station (output)
The following shows the time it takes for the output of a CC-Link remote I/O station to turn on (off) after a CPU
module device of the master station turns on (off).
For CC-Link, station-based block data assurance is disabled and the asynchronous mode is used.
• CC-Link IE Field Network station-based block data assurance is available.
Calculated
Calculation formula for asynchronous mode
value
(SM n2) + (LSf 1) +
Normal value
(SM n2) + (LSf 2) +
Maximum value
• CC-Link IE Field Network station-based block data assurance is not available.
Calculated
Calculation formula for asynchronous mode
value
(SM 1) + (LSf 1) +
Normal value
(SM 2) + (LSf 2) +
Maximum value
SM: Sequence scan time of the master station (including the link refresh time of the sending side)
LSf: Link scan time of CC-Link IE Field Network
n2: Value obtained by rounding up the decimal places of (LSf SM)
: Time for data transfer from CC-Link to CC-Link IE Field Network
T
LSc: Link scan time of CC-Link
Rio: Processing time of a CC-Link remote I/O station ( Manual for the CC-Link remote I/O station used)
+ (LSc 1) + Rio
T
+ (LSc 2) + Rio
T
+ (LSc 1) + Rio
T
+ (LSc 2) + Rio
T
Calculation formula for synchronous mode
(SM 1) + (LSf 1) +
+ (LSc 1) + Rio
T
(SM n2) + (LSf 1) +
+ (LSc 2) + Rio
T
Calculation formula for synchronous mode
(SM 1) + (LSf 1) +
+ (LSc 1) + Rio
T
(SM n2) + (LSf 1) +
+ (LSc 2) + Rio
T
APPENDICES
A
129