Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line
inside the control panel.
Master module
DA
Terminating
resistor
DB
DG
SLD
FG
(c) Grounding cables with a cable clamp
Use a shielded cable for external wiring and ground the shield of the shielded cable to the control panel with
the AD75CK cable clamp (Mitsubishi). (Ground the shield within 20 to 30cm from the module.)
For details on the AD75CK, refer to the following.
AD75CK-type Cable Clamping Instruction Manual
(4) External power supply
Use a CE-marked external power supply and ground the FG terminal.
(External power supply used for the tests conducted by Mitsubishi: TDK-Lambda DLP-120-24-1, IDEC
PS5RSF24)
136
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
Ver.1.10-compatible
CC-Link dedicated
cable
Inside the control panel
Module
20 to 30cm
AD75CK
Remote module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
Ver.1.10-compatible
FG
CC-Link dedicated
cable
Local module
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
FG