When the setting is configured with the assignment in the system, the start numbers of the link devices of each module
are as follows.
CPU module
X1000
X1020
Y1000
Y1020
W0
W10
W14
W1000
W1010
W1014
*1
The first 16 points of the link device are used as the area for the bridge module.
*2
This device is an unused area because a remote I/O station does not use a remote register.
CPU module
Master/local module
Device X
Remote input RX
X1000 to X101F
X1020 to X107F
Device Y
Remote output RY
Y1000 to Y101F
Y1020 to Y107F
Device W
Remote register RWr
W0 to WF
W10 to W13
RWr10 to RWr13
W14 to W1F
RWr14 to RWr1F
Device W
Remote register RWw
W1000 to W100F
W1010 to W1013
RWw10 to RWw13
W1014 to W101F
RWw14 to RWw1F
30
Master/local
module
RX0
RX20
RY0
RY20
RWr0
Rwr10
RWr14
RWw0
RWw10
RWw14
CC-Link IE Field Network
Bridge module
(station No.1)
Remote input RX
RX00 to RX1F
RX00 to RX1F
RX20 to RX7F
RX20 to RX7F
Remote output RY
RY00 to RY1F
RY00 to RY1F
RY20 to RY7F
RY20 to RY7F
Remote register RWr
RWr0 to RWrF
RWr0 to RWrF
RWr10 to RWr13
RWr14 to RWr1F
Remote register RWw
RWw0 to RWwF
RWw0 to RWwF
RWw10 to RWw13
RWw14 to RWw1F
Bridge module
Remote I/O station
RX0
RX20
RY0
RY20
*1
RWr0
RWr10
RWr14
*1
RWw0
RWw10
RWw14
Remote I/O station
(station No.1)
(1 station occupied)
Remote input RX
RX00 to RX1F
Remote output RY
RY00 to RY1F
Data such as the
operating status of
the bridge module
Data such as
the settings of
the bridge module
Remote device
station
RX0
RX0
RY0
RY0
*2
RWr0
*2
RWw0
CC-Link
Remote device station
(station No.2)
(3 stations occupied)
Remote input RX
RX00 to RX5F
Remote output RY
RY00 to RY5F
Remote register RWr
RWr0 to RWrB
Remote register RWw
RWw0 to RWwB