(2) Saving parameters
The information of a slave station performing data link through the automatic CC-Link startup is stored in the flash
ROM inside a bridge module using the slave station information saving function.
If the startup mode switch of a bridge module is set to PRM with the slave station information saved, the
parameters are set based on the saved data. Then CC-Link is started, and data link is performed.
(a) Operating procedure
The following is a procedure for saving slave station information.
1.
Start CC-Link using the automatic CC-Link startup function. ( Page 56, Section 7.2.1 (1) (a))
2.
Hold the startup mode switch in the SET position until the CC-Link RUN LED of the bridge module
turns off (about five seconds).
Slave station information is saved in the flash ROM inside the bridge module.
3.
The bridge module is reset and data link is started by executing the automatic CC-Link startup
again.
4.
Set the startup mode switch of the bridge module to PRM.
5.
The bridge module is reset and the parameters are set based on the saved slave station
information.
6.
The RUN LED and L RUN LED on the CC-Link side turn on.
7.
CC-Link is started.
If the startup mode switch of the bridge module is set to PRM when the power supply of the module is
turned off then on, the parameters are set based on the saved slave station information and CC-Link is
started.
● When the slave station information saving function is executed, the remote station having the largest station number
among connected stations is recognized as the last station. The unconnected stations having a smaller station number
than the last station are set as reserved stations in the parameter when the slave station information is saved.
(b) Parameters
The network parameters of CC-Link are set as listed below.
Item
Mode
Total Module Connected
Retry Count
Automatic Reconnection
Station Count
PLC Down Select
Data Link Faulty Station
Setting
Case of CPU STOP Setting
Description
Set the mode for the bridge module.
Set the number of CC-Link remote stations
connected.
Set the number of retries to be performed upon a
communication error.
Set the number of CC-Link remote stations that can
be returned to the network with one link scan from
the disconnection due to a communication error or
other factors.
Specify whether to stop or continue data link when
a stop error occurs in the CPU module of the
master station.
Specify whether to clear or hold the input data from
the data link faulty station.
Specify whether to refresh or compulsorily clear the
data output (transmitted) to the CC-Link remote
stations when the CPU module of the master
station is stopped.
CHAPTER 7 VARIOUS SETTINGS
Setting value
Remote Net (Ver.1 Mode)
Based on the actual connection
3 times
1 station
Stop
Clear the input data
Refresh
7
57