(5) CC-Link module
• To ground the Ver.1.10-compatible CC-Link dedicated cable, refer to Page 135, Appendix 5.1 (3) (b).
• Each power line connecting to the external power supply terminal or module power supply terminal must be
30m or less.
• Install a noise filter to the external power supply. Use the noise filter having an attenuation characteristic,
MA1206 (TDKLambda) or equivalent. Note that a noise filter is not required if the module is used in Zone A
defined in EN61131-2.
• Keep the length of signal cables connected to the analog input terminals of the following modules to 30m or
less. Wire cables connected to the external power supply and module power supply terminal in the control
panel where the module is installed.
• AJ65BT-64RD3
• AJ65BT-64RD4
• AJ65BT-68TD
• For the cable connected to the power supply terminal of the AJ65SBT-RPS, AJ65SBT-RPG or AJ65BT-
68TD, attach a ferrite core with attenuation characteristic equivalent to that of the ZCAT3035-1330 from TDK
Corporation. Twist the cable around the ferrite core by one as shown below.
• To supply the module power supply terminal of the AJ65BTB2-16R/16DR, AJ65SBTB2N-
8A/8R/8S/16A/16R/16S with power using the AC/DC power supply, follow as shown below.
• Install the AC/DC power supply in the control panel where the module is installed.
• Use a CE-marked AC/DC power supply and ground the FG terminals. (The AC/DC power supply used for
the tests conducted by Mitsubishi: TDK-Lambda Corporation: DLP-120-24-1)
• For the cable connected to the AC input terminal and DC output terminals of the AC/DC power supply,
attach a ferrite core. Twist the cable around the ferrite core by one as shown below. (Ferrite core used for
the tests conducted by Mitsubishi: NEC TOKIN Corporation: ESD-SR-250)