Mitsubishi Electric FX3G SERIES Programming Manual page 842

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Number and name
PLC Status
[D]8007
Operation frequency of M8007 is stored.
Momentary power
Cleared at power-off.
failure count
Default:
D8008
FX
Power failure
FX
detection
[D]8009
Minimum input device number of extension units in which
24V DC failed device
24V DC has failed.
*1.
The power failure detection time in FX
-
10ms for FX
-
100ms maximum for FX
from 10 to 100 ms.
-
5ms for FX
-
5ms for FX
not make any change in a sequence program.
-
For FX
Clock
Accumulated instruction-execution time from step 0
[D]8010
(in 0.1-ms units)
Present scan time
Minimum value of scan time
[D]8011
(in 0.1-ms units)
Minimum scan time
Maximum value of scan time
[D]8012
(in 0.1-ms units)
Maximum scan time
0 to 59 seconds
D8013
(for real time clock)
Second data
0 to 59 minutes
D8014
(for real time clock)
Minute data
0 to 23 hours
D8015
(for real time clock)
Hour data
1 to 31 days
D8016
(for real time clock)
Day data
1 to 12 months
D8017
(for real time clock)
Month data
2 digits of year data (0 to 99)
D8018
(for real time clock)
Year data
0 (Sunday) to 6 (Saturday)
D8019
(for real time clock)
Day-of-the-week data
*2.
A memory board having the real time clock function is required in FX
840
Content of register
*1
, FX
PLCs: 10 ms (AC power supply type)
3U
2N
, FX
PLCs: 5 ms
2NC
3UC
(DC power supply type)
PLCs used with a 100V AC power supply system. D8008 is set to 10ms by default.
2N
PLCs used with a 200V AC power supply system. D8008 can be set ranging
2N
PLCs used with a DC power supply type. Write "K-1" to D8008 for correction.
2N
PLCs used with a DC power supply type. System writes "K-1" to D8008 for correction. Do
2NC
and FX
PLCs, refer to Subsection 37.2.4.
3U
3UC
→Refer to Subsection 37.2.5
→Refer to Subsection 37.2.5.
→Refer to Subsection 37.2.5.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
→Refer to Subsection 37.2.7.
37 Operation of Special Devices (M8000 -, D8000 -)
FX
FX
3G
3U
and FX
PLCs is as follows.
2N
2NC
Same
Same
as on
as on
the
the
right
right
37.1 Special Device List (M8000 -, D8000 -)
Applicable model
Correspond-
FX
ing special
FX
FX
3UC
1S
1N
device
M8007
M8008
M8009
Same
Indicated value includes wait-
as on
ing time of constant scan opera-
the
tion (when M8039 is activated).
right
PLCs.
2NC
FX
FX
FX
2N
1NC
2NC
*2
*2
*2
*2
*2
*2
*2