Siemens SIMATIC S7-300 Reference Manual page 238

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Analog Modules
Behavior on failure of the supply voltage
Failure of the supply voltage of the analog modules is always indicated by the SF
LED on the module. Furthermore, this information is made available on the module
(entry in diagnostic buffer).
Triggering of the diagnostic interrupt depends on the parameter assignment (see
Section 4.7).
4.5.2
Effect of Range of Values of the Analog Values
Effect of errors on analog modules with diagnostics capability
Any errors that occur can lead to a diagnostics entry and a diagnostic interrupt with
analog modules with diagnostics capability and corresponding parameter
assignment. You will find the errors that might be involved in Section 4.16.
Effect of range of values on the analog input module
The behavior of the analog modules depends on where the input values lie within
the range of values.
Table 4-39 Behavior of the Analog Input Modules as a Function of the Position of the
Measured
Value In
Rated range
Overrange/und
errange
Overflow
Underflow
Beyond the
programmed
limit
1)
Only for modules with diagnostics capability and depending on parameter assignment
4-32
Analog Value within the Range of Values
Input Value
Measured
value
Measured
value
7FFF
H
8000
H
Measured
value
SF LED
Diagnostics
1)
1)
Flashes
Entered
1)
1)
Flashes
Entered
Programmable Logic Controllers S7-300 Module Data
Interrupt
Diagnostic
1)
interrupt
Diagnostic
1)
interrupt
Hardware
1)
interrupt
A5E00105505-03