Analog Modules
Suppression of interference, Limits of Error
Noise suppression for f = n
(f1 = interference frequency); n= 1, 2, ...
Common-mode noise
(U
< 50 V)
cm
Series-mode
interference (peak
value of interference
< rated value of input
range)
Crosstalk between the inputs
Operational limit (over entire
temperature range, referred
to input range)
Voltage input
Current input
Basic error (operational limit at 25° C referred to input
range)
Voltage input
Current input
Temperature error (with
reference to the input range)
Linearity error (with reference
to the input range)
Repeat accuracy (in the
steady state at 25°C, referred
to the input range)
4-80
(f1 ± 1%),
> 100 dB
> 90 dB
> 100 dB
U
= 0 / U
= ±50 V
CM
CM
±0.1% / ± 0.7%
±0.3% / ± 0.9%
±0.05%
±0.05%
±0.005%/K
±0.03%
±0.025%
Status, Interrupts, Diagnostics
Interrupts
Hardware interrupt when
limit has been exceeded
Diagnostic interrupt
Diagnostic functions
Group error display
Diagnostics information
read-out
Data for Selecting a Sensor
Input range (rated values)/Input resistance
Voltage
Current
Maximum input voltage for
voltage input (destruction
limit)
Maximum input current for
current input (destruction
limit)
Connection of the sensor
For measuring voltage
For measuring current
As two-wire transmitter
As four-wire transmitter
Load of the two-wire
transmitter
Programmable Logic Controllers S7-300 Module Data
Programmable
channels 0 and 2
Programmable
Programmable
Red LED (SF)
Possible
± 5 V
/ 2MΩ
1 to 5 V
/ 2MΩ
± 10 V
/ 2MΩ
0 to 20 mA;
/ 250 Ω
± 20 mA
/ 250 Ω
4 to 20 mA:
/ 250 Ω
max. 50 V continuous
max. 32 mA
Possible
Possible with separate
supply for the transmitter
Possible
max. 820 Ω
A5E00105505-03