Diagnostics Messages Of The Analog Output Modules - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Diagnostic messages of the analog output modules
The table below gives an overview of the diagnostic messages for the analog
output modules.
Table 4-47 Diagnostics Messages of the Analog Output Modules
Diagnostics Message
External auxiliary supply missing
Configuring/parameter assignment
error
Short-circuit to M
Wire-break
Note
A prerequisite for detecting the errors indicated by programmable diagnostic
messages is that you have assigned parameters to the analog module accordingly
in STEP 7.
Causes of errors and remedial measures for analog input modules
Table 4-48 Diagnostics Messages of the Analog Input Modules, Causes of Errors and
Remedial Measures
Diagnostics
Message
External load voltage
missing
Configuring/parameter
assignment error
assignment error
Common-mode error
Wire-break
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Possible Error Cause
Load voltage L+ of module missing
Illegal parameters transferred to
module
module
Potential difference U
CM
the inputs (M–) and reference
potential of measuring circuit (M
too high
Resistance too high in the sensor
connection
Open circuit between module and
sensor
Channel not connected (open)
LED
Diagnostics Ef-
fective for
SF
Module
SF
Channel
SF
Channel
SF
Channel
Feed supply L+
Check measuring range module
Reassign module parameter
between
Connect M– with M
)
ANA
Use different type of sensor or
connection, e.g. use conductors with a
larger cross-sectional core area
Close circuit
Disable channel group ("measuring
procedure" parameter
Connect channel
Analog Modules
Parameters can
be assigned
No
Yes
Yes
Yes
Remedy
ANA
4-73