Two-conductor connection of a resistance thermometer
With a two-conductor connection, you must insert jumpers on the module between
M
and I
+
Figure 4-17
Three-conductor connection to the SM 331; AI 8
With a three-conductor connection to the SM 331; AI 8
jumper between M
When connecting, make sure that the connected cables I
directly to the resistance thermometer.
Figure 4-18
Caution
!
Due to incorrect wiring of the three-conductor connection, unforeseen operation of
the module and dangerous conditions can result in the system.