hit counter script

Parameters Of The Sm 331; Ai 8 X 14 Bits High Speed - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Analog Modules
Table 4-60 Parameters of the SM 331; AI 8 x 14 bits High Speed
Parameter
Enable
Diagnostic interrupt
Hardware interrupt
upon limit violation
Fast Mode (only settable
if the 331-7HF01 was
registered in
synchronous operation
in the properties of the
DP slave)
Trigger for hardware
interrupt
Upper limit value
Lower limit value
Diagnostics
Group diagnostics
Measurement
Measuring Method
Measuring Range
Interference
Suppression
Channel groups
The channels of the SM 331; AI 8 x 14 bits High Speed are arranged in four
groups of two. You can only ever assign parameters to one channel group.
Die SM 331; AI 8 x 14 bits High Speed has a measuring range module for each
channel group.
The table below shows which channels are parameterized as a channel group in
each case. You will need the channel group number to set the parameters in the
user program with an SFC.
4-104
Value Range
Yes/no
Yes/no
Yes/no
Constraint possible due to measuring
range.
32511 to –32512
–32512 to 32511
Yes/no
Deactivated
U
Voltage
4DMU Current (4-wire transmitter)
2DMU Current (2-wire transmitter)
Refer to the reference manual, section
4.20.3, for the measuring ranges of the
input channels that you can set.
none; 400 Hz; 60 Hz; 50 Hz
Default
Settings
meter
No
Dynamic
No
No
Static
Dynamic
Static
No
U
Dynamic
"10 V
50 Hz
Programmable Logic Controllers S7-300 Module Data
Para-
Scope
Type
Module
Module
Channel
Channel
group
Channel or
Channel
group
group
A5E00105505-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF